TM 9-2350-287-20-12-19. TROUBLESHOOTING CHART (continued).w. AFES, CREW (continued).(7) AFES MEGOMETER TROUBLESHOOTINGPROCEDURES (continued).CONTINUED FROM EE. 4. Observe the fault LED on the CREW AFEST/A panel if it should go out.Do crew AFES T/A panel lights operate asindicated above?4Perform troubleshooting of SCEAorCREWAFES T/A panel (para 2-19.w(2)).F. 1. Test fire extinguisher activation circuitry bymomentarily activating CREW AFES T/Apanel MANUAL DISCHARGE switch locatedunder red switch guard.2. Corresponding LEDs on CREW AFES T/Apanel and on test box should illuminate toindicate the fire extinguishers which wereactivated, and personnel ventilation fanshould automatically turn on in exhaust mode8 to 10 seconds after fire extinguisheractivation.Does personnel ventilation fan turn on?G. 1. Set VENT FAN toggle switch on the testbox to OFF.2. Reset fire extinguisher simulators on testbox by pressing RESET switch on the test box.3. Repeat Step F.4. Observe VENT FAN LED on the test box.Does VENT FAN LED on test box illuminate for5 seconds after the 8-10 second fireextinguisher?Continued on next page2-364