TM 9-2350-287-20-12-19. TROUBLESHOOTING CHART (continued).w. CREW AFES (continued).(3) FIRE EXT. LED'S ARE LIT. FAULT LAMP REMAINSON (continued).CONTINUED FROM BIf flow indicator is protruding from valve,reset flow indicator by pushing it into thevalve body. If pressure is low, replace crewfire extinguishercylinder bottle (para 21-5).Verify problem is solved.c.WARNINGMake sure crew AFES T/A panelMaintenance switch is turned tovertical position before trouble-shooting AFES system. Failure tocomply will result in injury topersonnel or damage to vehicle.1. Disconnect wire harness 12352315 fromSCEA connector J2, and also disconnect wireharness 12352315 from actuator of defectivefire extinguisher(s).2. Check wire harness 12352315 circuits forcontinuity in the following order for applicablefire extinguisher bottle:FIRE EXTINGUISHER NO. 23P33P1AFBGcHFIRE EXTINGUISHER NO. 43P5AsBTcuContinued on next page2-354