TM 9-2350-277-20-2PREVENTIVE MAINTENANCE CHECKS AND SERVICES (PMCS), INCLUDINGLUBRICATION INSTRUCTIONS — Continued0155 00ITEMNO.INTERVALMAN-HOURITEM TO BECHECKED ORSERVICEDCREWMEMBERPROCEDUREEQUIPMENTNOT READY/AVAILABLEIF:70Semi-AnnualFixed FireExtinguisherCAUTIONFire extinguisher control valve sealed withsteel wire will not work. Make sure sealwire is made out of .020 light copper.a. Remove and weigh fixed fire extinguishercylinder (WP 0898 00).Extinguisher ismissing orseal/lockwiremissing orbroken, bottlesare overdue forhydrostatictest. Lock wireis not .020light copper.b. Recharge or exchange fire extinguisher if weightloss is more than 10 percent of charged weightstamped on bottle.c. Inspect fire extinguisher cylinder data plate toensure that a hydrostatic test has been performedwithin the past 12 years. Faulty extinguishers,or those beyond the test time limit (12 years),shall be declared unserviceable and replaced.CAUTIONFire extinguisher control valve sealed withsteel wire WILL NOT work. Use .020 thincopper wire.d. Before reconnecting cylinder, operate dischargehandles to be sure cables and controls workproperly.e. Install cylinder and replace copper seal wires(WP 0898 00).f. Replace discharge tubes that are crimped,plugged, or cracked (WP 0899 00).0155 00-121