VENTILATED  FACE  PIECE  SYSTEM  -  Continued
AUTOMATIC FIRE  EXTINGUISHiNG  SYSTEM  (AFES)

TM-9-2350-267-10 Carrier Personnel Full Tracked Armored M113A2 2350-01-068-4077 Carrier Command Post Light Tracked M577A2 2350-01-068-4089 Manual
Page Navigation
  284    285    286    287    288  289  290    291    292    293    294  
TM 9-2350-267-10 MALFUNCTION TEST OR INSPECTION CORRECTIVE ACTION Step 2. Step 3. Step 4. VENTILATED FACE PIECE SYSTEM - Continued Check rotary switch on each heater. Make sure rotary switch is turned fully clockwise. Turn  on  switch.  Power  lamp  should  light. Inspect outlet hose(s) and check for air flow. Notify Organizational Maintenance if hose is damaged or if air flow is re- stricted. Wait a few minutes after completing step 3, then check periodically for warm air flow. Air should warm within 15 minutes. Notify  Organizational  Maintenance  if  air  does  not  warm. UPPER REAR DOOR (BALLISTIC SHIELD) 38. UPPER REAR DOOR DOES NOT OPERATE WHEN SWITCH IS ENGAGED Step 1. Step 2. Step 3. Step 4. Check  flow  control  valve  setting. Turn valve fully counterclockwise and attempt operation. Refer to p 3-35 for adjustment   procedure. Check for hydraulic pressure between 100 and 300 psi. Notify  Organizational  Maintenance  if  pressure  is  not  within  range. Check that dump valve is closed. Close  dump  valve. Operate  BALLISTIC  SHIELD  directional  control  valve  manually. If  valve  can  be  operated  manually,  notify  Organizational  Maintenance  of electrical  failure.  If valve is not manually  operable,   notify   Organizational Maintenance  of  hydraulic  failure. 3-19







Western Governors University

Privacy Statement
Press Release
Contact

© Copyright Integrated Publishing, Inc.. All Rights Reserved. Design by Strategico.