TM 9-2350-247-20-3REPLACE WALTER KIDDE CONTROL VALVE — Continued 0528 00WARNINGSteel wire cannot be broken in an emergency. Make sure the wire is light copper. Failure of fireextinguisher to operate properly may cause injury to personnel or damage equipment.NOTE.020 copper safety wire is used to secure outside handle.7. Install new copper wire seal (1) through screw (2) and handle (3). Make sure wire is tight so it will break when handle ispulled. Crimp seal (4) on wire.8. Install adapter (5) in control valve (6).9. Install control valve (6) on cylinder (7). Secure with nut (8).10. Install tube (9) on adapter (5). Secure with nut (10).0528 00-5